Assessing air quality in cleanrooms and operating theatres

Met de techniek kan de luchtkwaliteit in cleanrooms en operatiekamers op voorhand getoetst worden, en dat voor verschillende uitvoeringen van het luchtbehandelingssysteem en voor verschillende gebruiksscenario’s.
Met de techniek kan de luchtkwaliteit in cleanrooms en operatiekamers op voorhand getoetst worden, en dat voor verschillende uitvoeringen van het luchtbehandelingssysteem en voor verschillende gebruiksscenario’s.

Air quality is crucial in cleanrooms and operating theatres. In both spaces, practical considerations and regulations set clear limits on the maximum particle concentration. Measurements are taken when the space is handed over to balance the airflow and test the performance of the air-handling system. However, if the results do not meet expectations, making changes to the installations afterwards is often very difficult and costly.

CFD simulations provide greater insight into airflow and the protected area than measurements taken at a few prescribed points in the space.

A one-off measurement at handover is also often not representative of the conditions once the space is actually in use. For example, the way a cleanroom is used may change over time, equipment in the space may be replaced or moved, and the number of people in the space can vary significantly. In an operating theatre, the position of the lights and clinicians may change, or equipment may be placed in the protected area, for instance. 

Taking measurements in the space is certainly useful, but it is also highly desirable to investigate and assess different (use) scenarios, preferably during the design process. 

Computational Fluid Dynamics

Computational Fluid Dynamics, or CFD, makes it possible to visualise airflow and particle concentrations in a space within a virtual 3D environment. This technique can be used to assess air quality in cleanrooms and operating theatres in advance, for different air-handling system configurations and usage scenarios. The aim is to ensure air quality while also using technical installations as efficiently as possible and improving thermal comfort for occupants. This provides confidence in the space’s performance from the outset and makes it more future-proof. 

Extensive validation project

CFD is a methodology originating in the aviation industry and has been extensively validated across various sectors and applications. However, airflow in cleanrooms and operating theatres is highly specific because air velocities are very low. For this reason, Actiflow has set up an extensive validation project in collaboration with Interflow, a leading manufacturer of operating theatres and cleanrooms. 

The validation process used a realistic operating theatre, including an air-handling system and objects such as lights, tables, monitors, doors, windows, a pendant and a service bridge. Measurements were then carried out in accordance with the RL7 guideline to determine the dimensions of the protected area. Further measurements mapped air velocity at various locations, and several operating theatre configurations were assessed, for example to determine the effect of the lights. The measurement results were then compared with the CFD results. This showed that the CFD results closely matched the velocity measurements taken. The protected area in the CFD simulations also corresponded almost exactly to the measurement points in the RL7 assessment. 

It also became clear that CFD simulations provide greater insight into airflow and the protected area than measurements taken at a few prescribed points in the space. The simulations make it possible to assess airflow and air quality at any point in the space. This gives them significant added value, both when designing new operating theatres or cleanrooms and when renovating existing spaces.

Practical experience

Actiflow has years of experience in carrying out CFD simulations for the design of operating theatres and cleanrooms. The results are used, for example, to advise hospitals and clinicians on the use of equipment and the positioning of lights in an operating theatre. Cleanroom builders receive advice on the design and balancing of fan filter units and the positioning of extract points, either with or without a raised floor.

Question about this story? Ask your question

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • ThemeSafe and reliable healthcare buildings
  • SubjectHospitals
Share this article

Advertisement

Follow on Bouwen aan de Zorg

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.