Ground-source energy is the ideal sustainable energy source for hospitals

Text and images Bodemenergie Nederland

Ground-source energy is the ideal sustainable energy source for hospitals

On Wednesday 9 October, the Gebruikersplatform Bodemenergie organised the workshop ‘The energy transition and the role of ground-source energy in hospitals’. And that role turns out to be particularly significant. In fact, according to many attendees and most of the speakers, ground-source energy is the ideal sustainable energy source for eventually taking hospitals completely off gas. The workshop took place at Spaarne Gasthuis in Hoofddorp, a good example of a hospital where ground-source energy plays a crucial role.

Spaarne Gasthuis has had an ATES system for many years. In recent years, however, the ATES installation has been upgraded, making it much more efficient and substantially reducing gas consumption. There is also considerable further potential that the hospital’s technical manager, together with its adviser and technical service provider Ates Control, aims to tap in the coming years. Ultimately, this should make it possible to balance the ground-source systems and fully disconnect the gas-fired boilers.

Visit to Spaarne Gasthuis

The workshop afternoon began with a presentation by Cor Wegman, team leader of the technical department at Spaarne Gasthuis, and Sander van der Wilt, who works for Ates Control and, in that role, supports the hospital in Hoofddorp. The hospital has two doublet systems, each with a capacity of 150 m3/h. Before the upgrade, there was one heat pump with a heating capacity of 350 kW and a cooling system using the air-handling units, based on the ground-source system, with a total capacity of 841 kW. There is also a central heating network supplied by a steam boiler and a high-efficiency boiler. The main problem with the old installation was that cold storage was not working well enough. Winters are not cold enough and the heat pump was underperforming, resulting in a heat surplus of 7.1 GWh on 1 January 2024. This surplus had grown to that level since 2014.

Taking a closer look at the system

As the installation was due for replacement, this was a good opportunity to review the overall configuration of the installations. With support from Ates Control, the system was analysed in detail. This revealed, among other things, that the heat pump is switched off when the outdoor temperature is between 8 and 16oC. The new design was based on several objectives.

  • The hospital wanted to supply as much heat as possible via the heat pumps, in order to reduce gas consumption as much as possible.
  • The hospital had to restore the balance in the ground by 2029.
  • The redundancy of the low-temperature system had to be increased.
  • And the hospital wanted to carry out the modifications while keeping the system operational.

A new system has now been installed in which the heat pump supplies 3,395 MWh (or 65%) of the heat. The flue-gas cooler and the central heating boilers still supply just over 30%. In the coming period, the hospital will also consider whether it can install a booster heat pump to supply central heating in summer and provide domestic hot water. If these measures prove feasible, the hospital will eventually be able to operate without gas.

Communication and collaboration

An important conclusion, Sander van der Wilt of Ates Control explained, was that the expertise of the hospital’s Technical Department was indispensable in designing the new, more efficient installation. Good communication and collaboration with the control engineers, Sauter in this hospital’s case, are also essential. In addition, it is vital to analyse in advance which users there are and what their requirements are. Good monitoring is also essential, as it provides insight into the possibilities. Finally, Van der Wilt said, a system of this kind in a hospital must be continually improved. Sufficient expertise of the right kind within the technical department is indispensable for this too.

Analysis of decarbonisation

Following this practical case study, Stefan van Heumen of TNO presented an analysis of the extent of decarbonisation among hospitals in the Netherlands as a whole. The figures from the Expertisecentrum Verduurzaming Zorg are important for this analysis. The Cure portfolio roadmaps have been submitted to the centre, and they contain a wealth of information. A total of 92 portfolio roadmaps have been submitted by 8 university medical centres, 63 general hospitals and 21 specialist institutions. 80 of the 92 roadmaps have now been finalised, of which 59 have been approved by the boards.

One notable finding is that the total floor area, currently 9.45 million m2 gross floor area, will fall by 6% by 2030. Planned new construction up to 2030 has now been mapped, but the picture is not yet clear everywhere for the years after that. The 92 institutions that have submitted roadmaps currently use an average of 28 m3 of gas per m2 gross floor area. Forecasts submitted by the institutions show that gas consumption will fall to an average of 10 m3 per m2 gross floor area in 2030. By 2030, CO2 emissions from all these hospitals will be around 68% lower than in the reference year.

Electricity consumption set to rise

Electricity consumption in hospitals is set to rise in the coming years. Hospitals currently use an average of 102 kWh per m2 gross floor area. According to the forecasts, electricity purchases will rise to an average of 136 kWh per m2 gross floor area. Compared with the reference year, total electricity consumption will increase by 26% in 2030. At the same time, on-site electricity generation from PV installations will increase from 19,725,000 kWh today to 51,603,000 kWh in 2030. This is about 9% of all electricity purchased.

Of the 92 hospitals, 33 plan to scale back their CHP installations by 2030. No fewer than 41 hospitals already have an ATES system or will bring one into use by 2040. 28 hospitals are connected to a heat network or will be connected by 2030. Interest in using aquathermal energy and geothermal energy is low. Just 4 hospitals have or are investigating one of these technologies. Many hospitals see thermal energy storage as the solution for reducing direct CO2 emissions.

The example of Maxima MC

After these figures, it was time for another practical case study, this time at Maxima MC in Veldhoven. Mark Raaijmakers works 3.5 days a week for the hospital as an energy and sustainability specialist. He describes himself as a committed ‘ATES believer’ and is working to make the hospital’s bivalent energy system, currently 70% ATES and 30% gas-fired, fully monovalent and therefore entirely based on ground-source energy. In recent years, the hospital in Veldhoven, next door to ASML, has grown substantially, from 44,000 m2 to 97,000 m2. The Maxima MC energy centre has run on ground-source energy since 2010, but performance was poor, Raaijmakers explained. Capacity was being used to only 50%. The ground was balanced, but the amount of heat and cold stored was very low. The heat pumps had a COP of just 2, despite being rated for 4.2. In short, energy performance was so poor that the investment was not being recouped.

Controls and system operation simplified

A series of modifications was then made to the above-ground system design. The controls and system operation were also substantially simplified, and the building services were optimised. This has already made it possible to achieve the theoretical capacity of the ground-source installation, while the heat pumps are now operating at their maximum COP of 4.2. The simpler installation also makes operation and management more effective. The amount of heat and cold now stored in the ground is considerably higher. As a result, Maxima MC has reduced its energy consumption by 54% compared with the previous situation in 2010. Direct CO2 emissions have fallen even further, by 64%, while Maxima MC has 200% more floor area than in the reference year.

Second ground-source doublet

To enable further growth, the hospital has applied for a permit for a second ground-source doublet. The hospital aims to meet the 2050 target set out in the Paris Agreement as early as 2030. Maxima MC wants to be an all-electric hospital by 2028. The 16,000 m2 of PV panels will generate 20 to 25% of its total annual electricity demand. The hospital’s entire heating and cooling demand must also be met by ground-source energy, including domestic hot water production. To share some further tips with the attendees, Raaijmakers listed what had initially gone wrong. Half of all the valves and pumps in the above-ground system turned out to be unnecessary. There were also layers of controls stacked on top of one another, instead of a single master control system for the entire building services installation. The design was not tailored to the building, meaning the entire installation could have been built for half the investment. “In short, follow the KISS principle: Keep it Simple & Stupid,” Raaijmakers concluded.

Knowledge is crucial

After a short break and a visit to the technical plant room at Spaarne Gasthuis, Romy Stijsiger and Niels de Groot of IF Technology took the floor. Their company is involved in numerous ground-source energy projects in the Netherlands in a wide range of roles. If one element is crucial across all this work, it is staff expertise. Anyone starting a ground-source energy project must not only acquire the necessary knowledge, Romy and Niels explained, but also know where to start and what to focus on. IF Technology’s staff identified five areas to focus on: Comfort, Sustainability, Effort, Costs and Security of supply. You also need a clear understanding of what management will involve. They distinguish between Energy management, Technical management and Legal management (BRL, environmental permits, etc.). Finally, every owner of a ground-source energy system needs to consider how responsibilities are divided at Operational, Tactical and Strategic levels. All these issues make clear that an organisation needs considerable expertise if it wants to manage all of this independently within a hospital.

Bronze, silver or gold

IF Technology helps many organisations by providing expertise and services. It offers ‘three flavours’ to keep clients’ knowledge up to date: Bronze, Silver or Gold. The Bronze support package provides light-touch support and periodic checks. The Silver package offers regular support, periodic checks and training programmes for staff. The most comprehensive service, Gold, provides extensive support, periodic checks, training programmes for staff and a broad range of services to take the burden off clients.

Rise in Legionella infections

The final speaker that afternoon was Kevin Kanters of Hydroscope, a company that comes under Brabant Water and is a sister company of Hydreco, an operator of ATES systems. Hydroscope focuses on preventing Legionella infections. Kanters opened his presentation with some worrying figures. Over the past ten years, the number of reported cases of Legionella pneumonia has risen sharply: from around 300 in 2013 to more than 600 in 2021 and 2022, and as many as 850 in 2023. The rise is due in part to climate warming, demographics and improved source investigations. Sources are increasingly wastewater treatment plants, cooling towers and bathing facilities, while drinking water installations are responsible in only a limited number of cases. At the same time, it is worrying that care institutions and hospitals are overrepresented in the sample results.

The need for hot tap water at 60oC

Kanters then discussed the need to heat hot tap water to at least 60oC. As heat pumps become more common, and we want to use them to heat tap water too, there are calls to lower the ‘safe 60oC’ threshold slightly. This would certainly improve heat pump efficiency significantly. He therefore put forward the proposition that 50oC is safe enough. Many people agreed. Others felt that it should still be possible to raise the temperature to 60oC at certain times.

Kanters also advocates designing tap water systems differently or using other methods of heating hot tap water. If we use fewer centralised hot tap water systems, it will also be less often necessary to maintain the 60oC threshold. Those responsible for managing these systems should also take a close look at whether all those hot water outlets are really necessary. Cor Wegman of Spaarne Gasthuis explained that they have already removed the hot water supply in many areas and installed decentralised hot water systems elsewhere. Various local hot water heating options were discussed: electric instantaneous water heaters, boiling water taps, fresh water stations and saltwater batteries.

Energy from drinking water

Finally, Kanters covered a number of statutory regulations and proposed amendments, for example to the Drinking Water Decree. It remains to be seen whether these will offer much additional scope in the coming years. One development involving drinking water that could offer greater scope for improving sustainability is harnessing the energy in drinking water. Cooling drinking water offers benefits on both sides. Colder drinking water is safer, and the heat extracted could potentially be used for space heating. Systems are also already available that continuously extract heat from drinking water and use that energy as a heat source for a heat pump or store it in an ATES system. Extracting heat from drinking water can also help to restore an imbalance in an ATES system.

Question about this story? Ask your question

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • ThemeSustainable healthcare buildings
  • SubjectGeneral
Share this article

Advertisement

Follow on Bouwen aan de Zorg

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.