Breda, Amphia Ziekenhuis | Low-consumption multistage/modular water treatment

To bring the quality of the mains water up to hospital standards, Amphia has opted for a multistage water treatment system. In the old building, the mains water is partly softened, filtered and given further treatment. In the new building, it undergoes additional treatment for use in, among other areas, the Central Sterile Services Department (CSSD). “Our systems stand out for their low life cycle costs,” says Norbert de Veen, sales account manager at supplier BWT Nederland.
Mains water is transported from the old building using booster pumps, then softened by around 50%. This is followed by an ultrafiltration system, which acts as a so-called gatekeeper against Legionella contamination. The water is then treated again using ultraviolet light.
Similar installations with additional reverse osmosis technology have been supplied for the new building. De Veen: “Here, the mains water treated in the old building is fully softened for use in, among other areas, the CSSD, and stripped of dissolved salts and minerals, by around 99% through double reverse osmosis using innovative membrane technology; ed. The water is then stored in a holding tank and treated with ultraviolet light. Our water purification systems use extremely little electricity, water and regeneration salt, which also means they have low life cycle costs, a key consideration in this project.” BWT manufactures most of its own equipment. The water treatment systems were set up by the installer and commissioned by BWT Nederland.
Question about this story? Ask your question
Keep following this
Get an email when a new story is published. No account needed.
- ThemeHospital construction and refurbishment
- SubjectInteriors